Digital Totalizing Flowmeter ADG
Orifice Type Flowmeter
Overview
The New Digital Totalizing Flowmeter consists of a base pipe with an orifice plate, a 3-way valve, a differential pressure sensor, and a flow transmitter. This flowmeter can be installed directly into the line without the need for separate pressure tapping pipes, resulting in low installation costs. It displays both current and cumulative readings on-site and offers various functions such as 4–20 mA and pulse outputs, making it convenient to use. With a built-in Smart Transmitter, it is a field-installable flowmeter with a wide range of settings.
Features
The 3-Way Orifice Valve features an integrated flow indicator and totalizer, making installation simple and reducing construction costs.
The on-site display and totalizer model allows you to view instantaneous flow and total flow once power is connected.
Equipped with a microprocessor, it allows you to program operating conditions to suit your specific application.
It can be installed in any orientation, whether horizontal or vertical.
Explosion-proof model available (optional)
With the use of connectors, it can be used with fluids under high-temperature and high-pressure conditions.
Explosion-proof type: Exd IIB T6
Selection of Type
Structural diagram
Flow range
SIZE |
Water(m³/h) |
AIR(Nm³/h) 760mmHg(A)20℃ |
|
|---|---|---|---|
Flow rate (Min~Max) |
Flow rate (Min~Max) |
||
⅜B |
10A |
0.1~0.5 |
0.08~4 |
½B |
15A |
0.2~1.0 |
2~10 |
¾B |
20A |
0.5~2.5 |
5~25 |
1B |
25A |
1.0~5.0 |
10~50 |
1¼B |
32A |
2~10 |
12~60 |
1½B |
40A |
3~15 |
20~100 |
2B |
50A |
5~25 |
40~200 |
2½B |
65A |
7~35 |
60~300 |
3B |
80A |
10~50 |
80~400 |
4B |
100A |
16~80 |
160~800 |
5B |
125A |
25~125 |
250~1250 |
6B |
150A |
30~200 |
350~1700 |
8B |
200A |
60~320 |
600~2800 |
10B |
250A |
90~480 |
900~5000 |
12B |
300A |
160~820 |
1600~7800 |
14B |
350A |
200~1000 |
2000~9500 |
16B |
400A |
300~1500 |
3000~14500 |
18B |
450A |
400~2000 |
4000~19000 |
20B |
500A |
500~2500 |
5000~24000 |
The pressure and temperature of the gas are 1 atm, 20°C.
For pressure PKgf/cm2, multiply this table by P+1.
The table above is the standard flow rate, and please discuss the other flow range with the headquarters.
Please refer to page 11 for Length.
Standard specification
category |
specification |
|
|---|---|---|
Applied fluid |
Liquid, Gas, Steam |
|
Flow range |
1:7 (standard), 1:5 (steam and special specifications) |
|
highest operating pressure |
20 kgf/cm2G (but for steam, 10 kgf/cm2G) |
|
Fluid temperature |
-20 to 120°C (optional up to 230°C) |
|
ambient temperature |
-10~50℃ |
|
detection unit |
measured differential pressure |
Low-pressure type : 0~500mmH2 O |
Medium-pressure type : 0~4,000mmH2 O | ||
High-pressure type : 0~16,000mmH2 O | ||
an on-site indicator |
instantaneous flow |
4Digit |
integrated flow rate |
10Digit (999999999 count) |
|
an output signal |
current output |
4-20mAC (maximum load resistance 600Ω) |
Pulse Output |
Insulated Open Collector Pulse (NPN method) |
|
Accuracy |
For liquids: ±2.0 F.S |
|
Power |
Input voltage |
AC 110/220V, 50/60Hz |
Power consumption |
4VA(Max) |
|
indication structure |
IP65 / Exd ⅡIBT6 |
|
Line connection |
1/2 PT |
|
Weight |
5.25Kg |
|
Materials Used
Part Name |
Material |
Material |
Material |
|
|---|---|---|---|---|
Base Socket |
SUS304 |
SUS316 |
PVC |
|
Orifice Plate |
SUS304 |
SUS316 |
PVC |
|
Indicator |
Aluminum Casting (ADC 12) |
|||
Differential Pressure Sensor |
Diaphragm |
SUS316L |
||
Other Wetted Parts |
SUS316L |
|||
O-RING |
VITON |
|||
Filling Fluid |
Silicone Oil |
|||
Pressure Transmission Section |
Body |
SCS314 |
||
Components |
SUS316 |
|||
O-RING |
TEFLON |
|||
Standard Specifications
Installation Precautions
1. The straight pipe sections for digital differential area flow meters are as follows.
Valve and T-fitting (D) |
Valve (D) |
|
|---|---|---|
Upstream |
10(6) |
14 |
downstream |
3 |
3 |
2. Installation Location
Avoid locations subject to vibration or direct sunlight.
For PVC, ensure that the surface temperature does not exceed 50°C.
3. When opening the neutral valve for zero adjustment, be sure to open the STOP valve first before opening the valve.
4. When using fluids under high-temperature or high-pressure conditions, be sure to use a connector pipe.
5. During operation, keep the neutral valve of the three-way valve closed, and fully open the valves on the High and Low sides.
How to Operate a 3-Way Valve
Keep valves 1 and 3 fully open at all times. / Keep the neutral valve (No. 2) closed at all times.
Detailed specification sheets are shown in the product images.
Catalogues
Digital Totalizing Flowmeter ADG
Digital Totalizing Flowmeter ADG: overview and buying guide
The Digital Totalizing Flowmeter ADG (model ADG) is made by AUTOFLOW and listed in our chemical range. Premium Emart sources it directly from the manufacturer and handles the quotation, inspection, export packing and international shipping, so you can buy it from anywhere in the world with a single point of contact.
Frequently asked questions
How much does the Digital Totalizing Flowmeter ADG cost?
Prices depend on the configuration, quantity and destination. Add the item to your RFQ list and we will send a free quotation with the unit price, lead time and shipping cost. There is no obligation to buy.
Can you ship the Digital Totalizing Flowmeter ADG to my country?
Yes. We export worldwide by sea, air or courier, with export packing and the commercial invoice, packing list and certificate of origin where required. The shipping options are shown in your quotation.
Is this a genuine AUTOFLOW product?
We purchase directly from AUTOFLOW or its authorised channels and confirm the model and specifications with the manufacturer before ordering.
What is the minimum order quantity?
For most items the minimum order is one unit. If the manufacturer sets a higher minimum, we tell you in the quotation.
Orifice Type Flowmeter
Overview
The New Digital Totalizing Flowmeter consists of a base pipe with an orifice plate, a 3-way valve, a differential pressure sensor, and a flow transmitter. This flowmeter can be installed directly into the line without the need for separate pressure tapping pipes, resulting in low installation costs. It displays both current and cumulative readings on-site and offers various functions such as 4–20 mA and pulse outputs, making it convenient to use. With a built-in Smart Transmitter, it is a field-installable flowmeter with a wide range of settings.
Features
The 3-Way Orifice Valve features an integrated flow indicator and totalizer, making installation simple and reducing construction costs.
The on-site display and totalizer model allows you to view instantaneous flow and total flow once power is connected.
Equipped with a microprocessor, it allows you to program operating conditions to suit your specific application.
It can be installed in any orientation, whether horizontal or vertical.
Explosion-proof model available (optional)
With the use of connectors, it can be used with fluids under high-temperature and high-pressure conditions.
Explosion-proof type: Exd IIB T6
Selection of Type
Structural diagram
Flow range
SIZE |
Water(m³/h) |
AIR(Nm³/h) 760mmHg(A)20℃ |
|
|---|---|---|---|
Flow rate (Min~Max) |
Flow rate (Min~Max) |
||
⅜B |
10A |
0.1~0.5 |
0.08~4 |
½B |
15A |
0.2~1.0 |
2~10 |
¾B |
20A |
0.5~2.5 |
5~25 |
1B |
25A |
1.0~5.0 |
10~50 |
1¼B |
32A |
2~10 |
12~60 |
1½B |
40A |
3~15 |
20~100 |
2B |
50A |
5~25 |
40~200 |
2½B |
65A |
7~35 |
60~300 |
3B |
80A |
10~50 |
80~400 |
4B |
100A |
16~80 |
160~800 |
5B |
125A |
25~125 |
250~1250 |
6B |
150A |
30~200 |
350~1700 |
8B |
200A |
60~320 |
600~2800 |
10B |
250A |
90~480 |
900~5000 |
12B |
300A |
160~820 |
1600~7800 |
14B |
350A |
200~1000 |
2000~9500 |
16B |
400A |
300~1500 |
3000~14500 |
18B |
450A |
400~2000 |
4000~19000 |
20B |
500A |
500~2500 |
5000~24000 |
The pressure and temperature of the gas are 1 atm, 20°C.
For pressure PKgf/cm2, multiply this table by P+1.
The table above is the standard flow rate, and please discuss the other flow range with the headquarters.
Please refer to page 11 for Length.
Standard specification
category |
specification |
|
|---|---|---|
Applied fluid |
Liquid, Gas, Steam |
|
Flow range |
1:7 (standard), 1:5 (steam and special specifications) |
|
highest operating pressure |
20 kgf/cm2G (but for steam, 10 kgf/cm2G) |
|
Fluid temperature |
-20 to 120°C (optional up to 230°C) |
|
ambient temperature |
-10~50℃ |
|
detection unit |
measured differential pressure |
Low-pressure type : 0~500mmH2 O |
Medium-pressure type : 0~4,000mmH2 O | ||
High-pressure type : 0~16,000mmH2 O | ||
an on-site indicator |
instantaneous flow |
4Digit |
integrated flow rate |
10Digit (999999999 count) |
|
an output signal |
current output |
4-20mAC (maximum load resistance 600Ω) |
Pulse Output |
Insulated Open Collector Pulse (NPN method) |
|
Accuracy |
For liquids: ±2.0 F.S |
|
Power |
Input voltage |
AC 110/220V, 50/60Hz |
Power consumption |
4VA(Max) |
|
indication structure |
IP65 / Exd ⅡIBT6 |
|
Line connection |
1/2 PT |
|
Weight |
5.25Kg |
|
Materials Used
Part Name |
Material |
Material |
Material |
|
|---|---|---|---|---|
Base Socket |
SUS304 |
SUS316 |
PVC |
|
Orifice Plate |
SUS304 |
SUS316 |
PVC |
|
Indicator |
Aluminum Casting (ADC 12) |
|||
Differential Pressure Sensor |
Diaphragm |
SUS316L |
||
Other Wetted Parts |
SUS316L |
|||
O-RING |
VITON |
|||
Filling Fluid |
Silicone Oil |
|||
Pressure Transmission Section |
Body |
SCS314 |
||
Components |
SUS316 |
|||
O-RING |
TEFLON |
|||
Standard Specifications
Installation Precautions
1. The straight pipe sections for digital differential area flow meters are as follows.
Valve and T-fitting (D) |
Valve (D) |
|
|---|---|---|
Upstream |
10(6) |
14 |
downstream |
3 |
3 |
2. Installation Location
Avoid locations subject to vibration or direct sunlight.
For PVC, ensure that the surface temperature does not exceed 50°C.
3. When opening the neutral valve for zero adjustment, be sure to open the STOP valve first before opening the valve.
4. When using fluids under high-temperature or high-pressure conditions, be sure to use a connector pipe.
5. During operation, keep the neutral valve of the three-way valve closed, and fully open the valves on the High and Low sides.
How to Operate a 3-Way Valve
Keep valves 1 and 3 fully open at all times. / Keep the neutral valve (No. 2) closed at all times.
Detailed specification sheets are shown in the product images.